Kray Cabling, Inc.


Rough-in Wiring Tests
Basic Telephony Cabling and
Security Wiring

Contents of this Document:

General Wiring Guidelines
Basic Testing Before Trim-Out

Diagram: Common Wiring Faults

Testing for Shorts and Opens (Continuity)

Testing for Crosses

Testing for Reversed Polarity (Rolls)

 


General Guidelines

Never begin installation of telephone wiring devices on a roughed-in job until the rough-in wiring has been tested for shorts, grounds, and opens.

When starting with a verified rough-in telephone wiring system, it is possible with proper methods to detect an error in device wiring at the time the error is made. This way, if device installation is completed and a problem shows up, it is likely that the fault lies in the device termination rather than with the building wiring.

Failure to install proper wiring and devices before occupancy can also cause serious disagreements and builder or homeowner dissatisfaction. These problems often arise when the occupant requests additional lines from the exchange carrier, only to be told the wiring is inadequate or "defective." Avoid these disputes by using proper materials and methods in the first place.

Some sophistication is required when troubleshooting telephone wiring systems because there are many ways problems can be created if the multi-color coded conductors are not properly matched, and devices not correctly wired. Polarity must always be observed, especially when making the transition from one color code to another. Most electrical house wiring problems show up immediately with a blown fuse or activated circuit breaker-but many telephone wiring system problems do not show up immediately, and often seem to get more complicated if repairs are attempted by untrained persons.

Always use proper materials to prevent trouble. The best wire choice is UL listed, NEC Article 800 compliant, four twisted-pair jacketed inside wire. Quad wire (pairs not individually twisted) is generally not suitable because it is only designed to carry one analog voice circuit (the other wires are for ground and accessory functions). Thus Quad wire should not be used with multiple lines, key systems, PBX systems, digital phone sets, or data applications.

Perform the following tests for each pair, after having made sure that the system is not connected to the network ("pull the plug" at the demarcation point first) or, more accurately, do not connect to the network prior to completely installing and testing all components.

In commercial applications, test horizontal runs prior to cross-connecting at the telecommunications closet, if one is present.

2T.2.1. BASIC TESTING BEFORE TRIM-OUT

1) Do a visual inspection of wire color matching to assure that the right access line is assigned to the right set of pairs, and that Tip (+) and Ring (-) are assigned to the proper pins.

2) Next, test each pair for a) continuity, b) shorts to ground, c) shorts to other pairs ("crosses") d) reversed polarity ("roll"). 

 


Diagram: Common Wiring Faults

 


2T.2.2. USING A BATTERY AND VOLT-OHM METER (RESIDENTIAL)  

2T.2.3. USING A SPECIALIZED CONTINUITY TESTER

Most continuity testers provide one or more LEDs to indicate shorts, opens, and polarity. The tester provides battery voltage and if a short exists, the appropriate LED will light.  

Note: This part of the test is usually not performed in high-volume commercial installations.

2T.2.4. USING A TONE GENERATOR AND INDUCTIVE PROBE

These tools are used together in identifying one specific pair from others. The tone generator (toner) is attached to one end of a vacant pair which must be traced to find the location of a fault, or identified so it can be spliced for a new circuit. Then the probe is used to "pick up" the tone, tracing the tone signal either along the wire or at the other end. For this test it is assumed that a continuity tester has already been used to verify continuity, polarity, and lack of shorts, yet a fault still exists.  

2T.2.5. TESTING FOR SHORTS AND OPENS (CONTINUITY)

The continuity setting of the Tone Test Set is used to locate shorts and verify continuity (no opens). A full short is indicated with a continuously lit green LED. A resistive or dirty open condition is indicated by a dim or blinking LED.  

2T.2.6. TESTING FOR CROSSES

A cross is a common fault caused by sloppy device wiring which allows a short to develop between two terminals. Usually this occurs because too much bare copper conductor is stripped and then the tail is not trimmed after connection.

Testing for crosses involves using the continuity mode of the toner to locate any electrical path from either conductor of one pair to either side of another pair. This is done as follows:  

If a cross is located before any devices are installed, it is likely that a nail or other fastener has been driven into the roughed-in wiring. Before the wiring can be completed, a cross must be located and repaired, or isolated out of the system.

2T.2.7. TESTING FOR SPLITS

A split occurs when two wires of a pair are split (separated) and improperly matched with wires from another pair (for example, tip lead of pair #1 matedwith ring lead of tip #2). A split will normally be located during the tests for opens and continuity previously described. Splits most often occur during splicing operations in low light, or when the splicer is tired or distracted.  

If the pair is split, the tone will remain strong when the wires are shorted.

If the pair is straight (not split), the tone will disappear when the wires are shorted.

Splits can also be isolated using a lineman's test set with the Tone Test Set. Refer to your lineman's test set instructions for details.


2T.2.8. TESTING FOR REVERSED POLARITY (ROLLS)

A rolled pair results when the tip and ring leads are reversed in connecting to the network. This may be done while splicing or installing a device. Proper polarity is essential for proper operation of some tone dials. A roll will not affect rotary dialing.

If a true tone telephone set does not produce tone beeps when the keypad is pushed, polarity may be reversed. If changing the polarity causes the set to beep as the keys are pushed, but numbers are not dialed (i.e., dial tone stays on), then the central office is not equipped to provide touch dialing on that particular line. Some telcos charge a monthly fee to provide touch dialing capability on a line; if the fee is not paid, they may inhibit tone dialing electronically.

If a push button set produces dial pulses when the keypad is operated, the set is not really a tone set. It may be called a "universal dialing set" but it does not signal to the central office with tones. When the keypad is operated, numbers are pulsed out just like a standard rotary dial. This type of set is easily identified by the letters "TE-19" (Terminal Equipment-Rotary) as the last three items in the FCC registration number printed on a label attached to the telephone. If the last three letters are "TE-T" (Terminal Equipment-Tone), then the set is a "true tone set" that signals the central office with tones instead of rotary dial pulses.

The Leviton Tone Test Set is equipped for polarity testing with a visual indicator. If dial tone is connected to the pair under test, the presence of a roll can be detected as follows:  

If this polarity test is performed with the toner connected to a pair using the test clips instead of the modular plug, you must be certain you are connecting the leads to the proper conductor. Tip is normally positive (connect the black lead) while ring is normally negative (connect the red lead).

If using central office battery (dial tone) for this test, you must be sure to check polarity during the dialtone BEFORE a number is dialed. Polarity will sometimes be reversed by the central office during completion of a call.

Some people prefer to test polarity with a buttset and tone test set, without dial tone connected. There are several methods that will work. The first method uses the two test devices together:  

Some installers prefer to use a 12-volt lantern battery as the source:  

If you discover the pair rolled on the network side, report the problem to the utility. Do not reverse the inside wiring system to accommodate a network reversal -- the network error may be detected at any time and "made normal." This would reverse your connection again, resulting in a callback.


© Copyright 1995 Leviton Manufacturing Co., Inc.

Kray Cabling, Inc.
510-236-5500 (Voice) 510-236-6100 (Fax)